Signet 2551 Display Magmeter
SAFETY INSTRUCTIONS
1. Depressurize and vent system prior to installation or removal.
2. Con rm chemical compatibility before use.
3. Do not exceed maximum temperature/pressure speci cations.
4. Wear safety goggles or faceshield during installation/service.
5. Do not alter product construction.
*3-2551.090-1*
3-2551.090-1 Rev. K 10/12 English
1. Description
The 2551 Magmeter measures the  ow rate in a full pipe by monitoring the voltage produced when the (conductive)  uid moves through
a magnetic  eld. Output options include a traditional frequency signal, a serial data (Digital (S
3
L)) output, and a 4 to 20 mA output.
The 2551 Magmeter is available in three sizes that will accommodate pipes from ½-inch through 36-inch diameters.
Select from three different material combinations to match the Magmeter to the application requirements.
English
1. Description 1
2. Specifi cations 2
3. Installation: Pipe fi ttings 3
3.1 Installation: Selecting a Location 3
4. Overview of 2551 Display versions 4
5. Wiring 5
5.1 Basic Wiring 5
5.2 Wiring: Mirror Relay 1 output 5
5.3 2551 and other manufacturer's instruments 5
5.4 Wiring to Signet Flow Instruments 6
5.5 Wiring Relays 7
6. View Menu 8
6.1 Resetting the Resetable Totalizer 8
6.2 Navigating the Menus 9
6.3 Keypad Functions 9
6.4 Security Code 9
7. Setup Menu 10
7.1 Averaging and Sensitivity 11
7.2 Bi-Directional Flow 12
7.3 Calibration Data 12
8. Calibration Menu 14
8.1 Volume method of calibration 14
8.2 Rate method of calibration 14
9. Relay Menus 15
9.1 Pulse Relay mode 15
9.2 Total Relay mode 15
9.3 High, Low, or Window Relay modes 16
10. Test Menu 17
11. Options Menu 17
11.1 Output Modes 17
12. Technical Information 18
12.1 Grounding 18
12.2 Maintenance 19
12.3 Troubleshooting 19
13. Ordering Information 20
FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT
IN THE SENSOR BEING EJECTED FROM THE PIPE!
DO NOT USE ANY TOOLS ON THE RETAINING CAP.
HAND TIGHTEN ONLY.
LUBRICATE O-RINGS WITH A NON-PETROLEUM BASED,
VISCOUS LUBRICANT (GREASE) COMPATIBLE WITH
THE SYSTEM.
DO NOT USE THREAD SEALANT OR LUBRICANTS ON
THE RETAINING CAP OR ON THE PLASTIC FITTING
THREADS.
IF LEAKING IS OBSERVED FROM THE RETAINING CAP,
IT INDICATES DEFECTIVE OR WORN O-RINGS ON THE
SENSOR. DO NOT ATTEMPT TO CORRECT BY FURTHER TIGHTENING.
DO NOT USE thread sealant
or lubricants on the fitting threads!
Do not use any tools to
tighten the yellow retaining cap.
DO NOT USE thread sealant or
lubricants on retaining cap!
Lubricate O-rings with a
non-petroleum based, viscous
lubricant (grease) compatible
with the system.
Contents
WARNING!
Vista de pagina 0
1 2 3 4 5 6 ... 19 20

Indice de contenidos

Pagina 1 - Signet 2551 Display Magmeter

Signet 2551 Display MagmeterSAFETY INSTRUCTIONS1. Depressurize and vent system prior to installation or removal.2. Con rm chemical compatibility be

Pagina 2 - 2. Specifi cations

10 2551 Magmeter K-Factor 060.000 > K-Factor: See the charts in section 7.3 for values in pulses per U.S. gallon or in pulses per

Pagina 3 - 32551 Magmeter

112551 MagmeterSensitivity• The SENSITIVITY setting determines how the 2551 responds to sudden surges in the  ow rate. It "overrides" the

Pagina 4 - 4 2551 Magmeter

12 2551 Magmeter 7.3 Calibration Data: K-Factors7.2 Bi-Directional Flow• The 2551 magmeter is designed to measure bi-directional  ow.• The forwar

Pagina 5 - 26.4 VDC

132551 MagmeterIron SaddlesBronze and Copper Tees and Brazolets7.3 Calibration Data: K-FactorsCarbon Steel Tees and Weld-o-LetsStainless Steel Tees a

Pagina 6 - I/O Module 3-8900.401-X

14 2551 Magmeter 8. Calibration MenuThe K-Factors published in this manual assume that the  ow conditions in the pipe are ideal.Many factors that af

Pagina 7 - 72551 Magmeter

152551 Magmeter9. Relay MenusMagmeter models 3-2551-21 and -22 have two dry contact relays (Relays 1 and 2) and one Solid State relay (Relay 3).Any of

Pagina 8 - 6. View Menu

16 2551 Magmeter The values shown for each menu item represent the factory standard setting. All 2551 magmeters are packaged with these settings.The

Pagina 9 - WRITE IT DOWN!

172551 Magmeter11. Options MenuThe Options Menu contains those features and settings that will normally be set one time and then seldom changed. These

Pagina 10 - 7. Setup Menu

18 2551 Magmeter Grounding rings on plastic pipe (Install between flanges) or metal straps on metal pipe Sensor Grounding ring (10 cm to 1.3 m) (10 c

Pagina 11 - Velocity

192551 Magmeter12.3 TroubleshootingTroubleshooting with the RED and BLUE LEDsNo Lights: The power is off or the sensor is not connectedSolid Blue: The

Pagina 12 - 12 2551 Magmeter

2 2551 Magmeter General• Pipe size range: DN15 to DN900 (½ to 36 in.)• Flow Range Minimum: 0.05 ms (0.15 ft/s) (Bi-directional) Maximum: 1

Pagina 13 - 132551 Magmeter

Georg Fischer Signet LLC, 3401 Aero Jet Avenue, El Monte, CA 91731-2882 U.S.A. • Tel. (626) 571-2770 • Fax (626) 573-2057For Worldwide Sales and

Pagina 14 - 8. Calibration Menu

32551 Magmeter3.1 Installation: Selecting a Location• The 2551 requires a full pipe and a fully developed turbulent  ow pro le for accurate measur

Pagina 15 - 9. Relay Menus

4 2551 Magmeter 4. Overview of 2551 Display Magmeter2551 Display Magmeters use a dual-sided electronics module and dual conduit ports. Unused ports

Pagina 16 - Relay deactivated

52551 Magmeter5. Wiring5.1 Basic Wiring2551 Magmeter4.5-26.4VDCRelay 1Relay 2NO1NO2NO3NC1NC2NC3C1C2C3Relay 3V+V-+ VDC- VDCAux Pwr3Frequency OutFrequen

Pagina 17 - 10. Test Menu

6 2551 Magmeter - + 12-24 V 10 W 12-24 V 10 W 4-20 mA Total reset AUX output PLS output 1 2 Gnd - + + + Gnd Freq. IN Sen. Pwr. Freq. IN Iso. Gnd

Pagina 18 - 12. Technical Information

72551 MagmeterRelay 3 is a solid state relay. It can be applied exactly the same as a dry contact relay, but the current rating is 0.2 A (200 mA) maxi

Pagina 19 - 192551 Magmeter

8 2551 Magmeter 6. View MenuThe VIEW menu contains all of the basic information available from the Magmeter.• The normal operating display shows the

Pagina 20 - 13. Ordering Information

92551 Magmeter6.2 Navigating the Menus6.4 Security CodeThe 2551 has a security code that can be programmed to any four-digit numerical value.• The f

Comentarios a estos manuales

Sin comentarios